Description
Overview:
Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels.
Features:
- Mount horizontally, vertically or at any angle in between.
- Provide quick electrical hookup with 1 in NPT threaded conduit fitting and color-coded lead wires.
- Reduced nuisance shutdowns by wiring two in parallel.
- C7012A,E meets NEMA 4 standards with viewing window rated to 20 psi.
Product Specifications
| Application | Gas, Oil or Coal fired burners |
| Dimensions (in.) | 5 1/4 in. diameter (includes mounting flange) x 7 7/32 in. long |
| Dimensions (mm) | 133 mm diameter (includes mounting flange) x 183 mm long |
| Includes | Cast case and cover |
| Use With | Flame Amplifiers: R7247A, B; R7847A, B; R7257 |
| Weight (lb) | 4.25 lb |
| Weight (kg) | 1.9 kg |
| Comments | For use with rectification flame signal amplifiers |
| Mounting | 1 in. NPT |
| Electrical Ratings | 120 Vac |
| Frequency |
50 Hz; 60 Hz |
| Approvals, Underwriters Laboratories Inc. | Listed: File No. MP 268; Guide No. MCCZ |
| Approvals, Canadian Standards Association | Certified: Master Report LR95329-1 |
| Electrical Connections | 4 NEC Class 1 Color-coded lead wires. |
| Power Consumption | 2.5 W |
| Approvals, Swiss RE | Acceptable |
| Approvals, Factory Mutual | Approved: Report No. 14740.01 |