Description
Overview: Microprocessor-based integrated primary burner control for automatically fired gas, oil or combination fuel single burner applications. Provides level of safety, functional capability and features beyond conventional controls.
Features:
- Includes Shutter Drive Capability, Alarm sounds when Reset pushed.
- Functions include automatic burner sequencing, flame supervision, system status indication, system or self diagnostics and troubleshooting.
- Subbase and amplifier are required for operation.
- Options include PC interface, keyboard display module, DATA CONTROLBUS™ MODULE, remote display module, first-out expanded annunciator, and COMBUSTION SYSTEM MANAGER™ software.
- Five LEDs provide sequence information.
- Interchangeable plug-in flame amplifiers.
- Optional local or remote annunciation of operation and fault information.
- Nonvolatile memory retains history files and sequencing status after power loss.
- Optional remote reset capability.
- Optional report generation.
- Selectable relight or lockout on loss of flame.
- Flame Establishing Period - Pilot: Fixed 4 sec or 10 sec PFEP
- Flame Establishing Period - Main: Intermittent
Here's the optimized description for the RM7890B1030:
Suggested Description
The Honeywell RM7890B1030 is a microprocessor-based on-off primary burner control for automatically fired gas, oil, coal, or combination fuel single burner applications. It is the shutter drive variant of the 7800 Series RM7890B family, adding built-in shutter drive capability and an audible alarm on reset — two features not present on the base RM7890A models. This unit is discontinued by Honeywell (discontinued April 8, 2022) — new old-stock units are available here for maintenance and replacement use.
As a full primary burner control, the RM7890B1030 handles automatic burner sequencing, flame supervision, safe-start checks, safety lockout, and load switching — making it the complete control center of a flame safeguard system. A compatible wiring subbase and flame signal amplifier are required; the display module is sold separately.
Key Features
- Shutter drive capability — built-in output to operate UV scanner shutters; requires 220-240V to 120VAC 10VA minimum stepdown transformer for shutter drive
- Audible alarm on reset — alarm sounds when the Reset button is pushed, a distinguishing feature of the B-series vs A-series models
- Fixed 4-second or 10-second PFEP — pilot flame establishing period is fixed (not jumper-configurable in the field the same way as selectable models)
- Intermittent pilot — pilot established at startup and extinguished once main flame is proven
- Intermittent main flame establishing period
- Selectable relight or lockout on loss of flame — configurable behavior via site jumper
- Five status LEDs — real-time sequence indication for Power, Pilot, Flame, Main, and Alarm
- Interchangeable plug-in flame amplifiers — supports UV, IR, and rectification detection
- Nonvolatile memory — retains history files and lockout status through power loss
- Lockout and running interlocks
- Optional remote reset capability
- Supports gas, oil, coal, or combination fuel applications
Specifications
| Spec | Value |
|---|---|
| Voltage | 120 VAC (+10%, -15%) |
| Frequency | 50/60 Hz (±10%) |
| Pilot Type | Intermittent |
| Pilot FEP | Fixed 4-sec or 10-sec |
| Main FEP | Intermittent |
| Preignition | No |
| Operating Temperature | -40°F to 140°F (-40°C to +60°C) |
| Weight | 2.75 lbs |
| UPC | 085267204620 |
| Alternate Part Numbers | RM7890B2030 |
| Status | Discontinued April 8, 2022 |
Required & Compatible Components
- Wiring Subbase: Q7800A or Q7800B Universal Wiring Subbase (required)
- Flame Signal Amplifier: R7847, R7848, R7849, R7851, R7852, R7861, or R7886 (required)
- Shutter transformer: 220-240V to 120VAC, 10VA minimum (required if using shutter drive)
- Display (optional): S7800A1142 Keyboard Display Module — enables programmable postpurge and fault history
- Optional add-ons: PC interface, Data ControlBus™ Module, remote display module, first-out expanded annunciator, Combustion System Manager™ software
How the RM7890B1030 Differs from Related Models
The RM7890 family spans several variants — here's how the B1030 fits in:
- vs. RM7890A1015 — the A1015 has no shutter drive output and no audible alarm on reset; the B1030 adds both
- vs. RM7890B1014 — the B1014 has a shutter terminal available but no active shutter drive output; the B1030 includes a full shutter drive
- vs. RM7890B1048 — the B1048 is the current active replacement for applications requiring shutter drive output; the B1030 is discontinued
- vs. RM7890A1056 — similar to the A1015 but with fixed PFEP; neither has shutter drive
Common Applications
The RM7890B1030 is used in commercial boilers, industrial heating equipment, process burners, and combustion systems where a UV scanner with a motorized shutter is installed — typically in applications where shutter-equipped C7027, C7035, or similar Honeywell UV detectors are used. It is suited to single-burner systems requiring automatic startup, proven pilot, and safety lockout with shutter operation integrated into the control sequence.
Important Notes
- This product is discontinued by Honeywell — units available are new old-stock; no factory reorders are possible
- Subbase and amplifier are required and are not included
- The Keyboard Display Module is not included — order S7800A1142 separately if programmable postpurge or on-board fault history is needed
- Not weather-tight — must be protected by an approved enclosure when installed outdoors